Customization: | Available |
---|---|
Application: | High-voltage |
Material: | Composite Polymer |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
No. | Insulator model | Figure No. |
Nominal voltage kV |
Mechanical failing load | Installation height mm |
Arc distance mm |
Creepage distance mm | Lightening impulse withstanding voltage kV (peak value) No less than |
Power frequency withstanding voltage kV (effective value)no less than |
Center distance of installation hole D |
Bore diameter of installation holed D |
||
Bending P0 kN | Torsion kN.m | 1min Dry withstanding |
1min Wet withstanding |
||||||||||
1 | FZSW-12/12.5 | 1 | 10 | 12.5 | 2.5 | 350 | 250 | 650 | 75 | 42 | 30 | 127 | 18 |
2 | FZSW-40.5/10 | 2 | 35 | 10 | 2.5 | 445 | 350 | 900 | 185 | 100 | 80 | 127 | 18 |
3 | FZSW-126/10 | 3 | 110 | 12.5 | 6.0 | 1220 | 1080 | 3200 | 450 | 265 | 185 | 127 | 18 |
4 | FZSW-252/8 | 3 | 220 | 8 | 4.0 | 2300 | 2160 | 6300 | 950 | 495 | 395 | 127 | 18 |